Wide-span cable ladder, additional transverse rigidity due to welded rungs made of profile rungs. Electrical conductivity tested according to DIN EN 61537.
Do not walk upon!
Continously hot galvanized (Sendzimir process) (DIN EN 10346)
height | width | length | t material thickness | A cross section area | QLKdistributed load power cable | weight | ||
---|---|---|---|---|---|---|---|---|
WL 200-30S | 202 mm | 300 mm | 6000 mm | 2,00 mm | 430 cm² | 1,20 kN/m | 57,98 kg | |
WL 200-40S | 202 mm | 400 mm | 6000 mm | 2,00 mm | 574 cm² | 1,61 kN/m | 59,76 kg | |
WL 200-50S | 202 mm | 500 mm | 6000 mm | 2,00 mm | 719 cm² | 2,01 kN/m | 61,52 kg | |
WL 200-60S | 202 mm | 600 mm | 6000 mm | 2,00 mm | 863 cm² | 2,42 kN/m | 63,23 kg | |
WL 200-20S | 202 mm | 200 mm | 6000 mm | 2,00 mm | 285 cm² | 0,80 kN/m | 56,22 kg |
Hot-dip galvanized, according to BS 729 (DIN EN ISO 1461)
height | width | length | t material thickness | A cross section area | QLKdistributed load power cable | weight | ||
---|---|---|---|---|---|---|---|---|
WL 200-30F | 202 mm | 300 mm | 6000 mm | 2,00 mm | 430 cm² | 1,20 kN/m | 62,03 kg | |
WL 200-40F | 202 mm | 400 mm | 6000 mm | 2,00 mm | 574 cm² | 1,61 kN/m | 63,94 kg | |
WL 200-50F | 202 mm | 500 mm | 6000 mm | 2,00 mm | 719 cm² | 2,01 kN/m | 65,82 kg | |
WL 200-60F | 202 mm | 600 mm | 6000 mm | 2,00 mm | 863 cm² | 2,42 kN/m | 67,70 kg | |
WL 200-20F | 202 mm | 200 mm | 6000 mm | 2,00 mm | 285 cm² | 0,80 kN/m | 60,15 kg |